Pro-face LT Series Przewodnik Instalacji

Przeglądaj online lub pobierz Przewodnik Instalacji dla Telewizory i monitory Pro-face LT Series. Pro-face LT Series Installation guide Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 16
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 0
1
LT-3300 Series
Installation Guide
Package Contents
(1) LT Unit (1)
(2) English and Japanese Installation Guides
(one of each) <This Guide>
(3) Warning/Caution Information (1)
(4) English and Japanese EX Module
Hardware Manual
*1
(1)
(5) Installation Gasket (1, attached to the LT
unit)
(6) Installation Fasteners (Set of 4)
(7) DIO Connector (1)
(8) Power Connector (1)
(9) USB Cable Clamp (1 set)
(Holder: 1, Cover: 1)
(10) EX module
*1
Hook (only for LT-3300 Series) (1)
This unit has been carefully packed, with
special attention to quality. However, should
you find anything damaged or missing,
please contact your local LT distributor
immediately.
About the Manual
For the detailed information on LT3000
series, refer to the following manual.
LT3000 Series Hardware Manual
Maintenance/Troubleshooting
GP-Pro EX Reference Manual “Con-
trolling External I/O”
Device/PLC Connection Manual
LT3000 Series Hardware Manual can be
selected from the help menu of GP-Pro EX or
downloaded from Pro-face Home Page.
URL
http://www.pro-face.com/otasuke/
Caution
Be sure to read the “Warning/Caution
Information” on the attached sheet before
using the product.
*1 The EX module is an extension I/O unit for the LT
3000 series. To use the EX module, be sure to read
the supplied manual.
Przeglądanie stron 0
1 2 3 4 5 6 ... 15 16

Podsumowanie treści

Strona 1 - About the Manual

1LT-3300 SeriesInstallation GuidePackage Contents(1) LT Unit (1)(2) English and Japanese Installation Guides (one of each) <This Guide>(3) Warni

Strona 2 - Part Names and Functions

10Installations1. Installation Requirements• For easier maintenance, operation, and improved ventilation, be sure to install the LT at least 100 mm [3

Strona 3 - General Specifications

11• Tightening the screws with too much force can damage the LT unit’s plastic case.• The necessary torque is 0.5N•m.• Be sure to insert installation

Strona 4 - External Interfaces

12• Do not solder the wire itself. This could lead to a bad or poor contact.• Insert each wire completely into its opening. Failure to do so can lead

Strona 5 -  DIO Interface (Connector)

13(3) Attach the Power connector (Plug) to the Power Connector.2. Power Supply Cautions• Input and Output signal lines must be sepa-rated from the pow

Strona 6 - • Input Derating

144. Input/Output Signal Line Cautions• All LT Input and Output signal lines must be separated from all operating circuit (power) cables.• If this is

Strona 7 -  Output Specifications

15(3) Insert the USB cable into the USB Host Interface.(4) Attach the USB cover to the USB host interface. Hold the USB cover in the orientation shown

Strona 8

16COUPER LE COURANT OU S’ASSURER QUE L’EMPLACEMENT EST DESIGNE NON DANGEREUX”.(5) In the case of use in Hazardous Locations, be sure to check that the

Strona 9

2Part Names and FunctionsName DescriptionAStatus LEDB DIO Interface (DIO) The interface to external I/O equipmentCAUX Unit Interface/Expansion Unit (E

Strona 10 - Installations

3General Specifications Electrical Specifications Environmental SpecificationsPower SupplyInput Voltage DC24VRated Voltage DC19.2 to 28.8VAllowable

Strona 11 -  Connecting the DIO Cable

4External Interfaces• For instructions on how to connect to other devices, always refer to the “GP-Pro EX Device/PLC Connection Manual”.• Always conne

Strona 12 -  Power Cord Specifications

5 DIO Interface (Connector)• When preparing the cable to connect the wiring, check the pin numbers inscribed onthe DIO Connector.• Parenthesized sign

Strona 13 - 2. Power Supply Cautions

6 Input Specifications• Input DeratingUsing LT input voltage that exceeds the rated voltage, the input ON voltage, the number of input points or the

Strona 14 - To prevent the USB cable

7• Input Circuit Output SpecificationsOutput Terminal OUT0 to OUT3 OUT4 to OUT15Rated Voltage DC24VAllowable Voltage Range DC20.4V to DC28.8VOutput M

Strona 15 - UL/c-UL/CSA Approval

8•LT330∗-∗1-D24-K Output Circuit (Sink type)• Since the output terminals are not electrically protected, an output line might be short-cir-cuited or a

Strona 16 - Revision

9 High-Speed Counter / Pulse Catch Input SpecificationsDIO Standard Input/Output is used as a High-Speed Counter Input. The setup is done by the GP-P

Komentarze do niniejszej Instrukcji

Brak uwag