1LT-3300 SeriesInstallation GuidePackage Contents(1) LT Unit (1)(2) English and Japanese Installation Guides (one of each) <This Guide>(3) Warni
10Installations1. Installation Requirements• For easier maintenance, operation, and improved ventilation, be sure to install the LT at least 100 mm [3
11• Tightening the screws with too much force can damage the LT unit’s plastic case.• The necessary torque is 0.5N•m.• Be sure to insert installation
12• Do not solder the wire itself. This could lead to a bad or poor contact.• Insert each wire completely into its opening. Failure to do so can lead
13(3) Attach the Power connector (Plug) to the Power Connector.2. Power Supply Cautions• Input and Output signal lines must be sepa-rated from the pow
144. Input/Output Signal Line Cautions• All LT Input and Output signal lines must be separated from all operating circuit (power) cables.• If this is
15(3) Insert the USB cable into the USB Host Interface.(4) Attach the USB cover to the USB host interface. Hold the USB cover in the orientation shown
16COUPER LE COURANT OU S’ASSURER QUE L’EMPLACEMENT EST DESIGNE NON DANGEREUX”.(5) In the case of use in Hazardous Locations, be sure to check that the
2Part Names and FunctionsName DescriptionAStatus LEDB DIO Interface (DIO) The interface to external I/O equipmentCAUX Unit Interface/Expansion Unit (E
3General Specifications Electrical Specifications Environmental SpecificationsPower SupplyInput Voltage DC24VRated Voltage DC19.2 to 28.8VAllowable
4External Interfaces• For instructions on how to connect to other devices, always refer to the “GP-Pro EX Device/PLC Connection Manual”.• Always conne
5 DIO Interface (Connector)• When preparing the cable to connect the wiring, check the pin numbers inscribed onthe DIO Connector.• Parenthesized sign
6 Input Specifications• Input DeratingUsing LT input voltage that exceeds the rated voltage, the input ON voltage, the number of input points or the
7• Input Circuit Output SpecificationsOutput Terminal OUT0 to OUT3 OUT4 to OUT15Rated Voltage DC24VAllowable Voltage Range DC20.4V to DC28.8VOutput M
8•LT330∗-∗1-D24-K Output Circuit (Sink type)• Since the output terminals are not electrically protected, an output line might be short-cir-cuited or a
9 High-Speed Counter / Pulse Catch Input SpecificationsDIO Standard Input/Output is used as a High-Speed Counter Input. The setup is done by the GP-P