Pro-face GP4107G1D Dokumentacja Strona 13

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 73
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 12
12
(4) Control Drawing of USB (Type A) Interface (USB1)
The information below concerns the use of the USB interface used in Class I, Division 2, Groups A, B, C,
and D hazardous locations (from Doc No. 3910017-USB).
Notes:
1. Nonincendive Circuit Parameters:
USB interface:
Voc = 5.25 V
Isc = 0.7 A
Ca = 16 µF
La = 10 µH
2. Selected Associated Nonincendive Field Wiring Apparatus shall satisfy the following:
3. If the electrical parameters of the cable are unknown, the following values may be used:
Capacitance = 60 pF/ft
Inductive = 0.20 µH/ft
4. Nonincendive Field Wiring must be installed in accordance with article 501.10(B) of the National
Electrical Code ANSI/NFPA 70.
5. Nonincendive Field Wiring Apparatus shall not contain or be connected to another source of power.
(5) USB (mini-B) Interface (USB2) is for temporary connection only during maintenance and setup of the
device. Do not use, connect, or disconnect unless area is known to be non-hazardous. Connection or dis-
connection in an explosive atmosphere could result in an explosion.
Associated Nonincendive Field Wir-
ing Apparatus for USB (Type A)
interface of the GP-4100 Series
-
Nonincendive Field Wiring Appara-
tus
Voc Vmax
Isc lmax
Ca
Ci + C cable
La
Li + L cable
USB Pin Description
1. Vcc
2. D-
3. D+
4. GND
(See Note 1 for details)
Shield GND
Nonincendive Field
Wiring Apparatus
1 2 3 4
Przeglądanie stron 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 72 73

Komentarze do niniejszej Instrukcji

Brak uwag